1. Application range

This series of zero-sequence over-current and over-voltage relays are used in generators, transformers and power transmission lines as zero-sequence over-current and over-voltage protection.


2. Model definition

20140219202622652265.jpg


3. Working principle and main performance

3.1 Working principle:

The AC voltage or AC current is converted by the converter to the AC voltage required by the series of relays; then the harmonics other than 50HZ are filtered through the 150HZ band stop and 50HZ band pass; then the DC voltage is converted into the setting circuit through rectification and filtering; The loop changes the setting value by changing the magnification of the operational amplifier; the output voltage UZ of the setting loop is compared with the threshold voltage UB through the level detector; then the output of the relay J is driven to act.

3.2 The action process of zero sequence overcurrent and zero sequence overvoltage relay (take AK11 structure relay as an example):

3.2.1 For the zero-sequence over-current relay in normal operation, UZ<UB, relay J will not operate, the moving contacts 1-3 and 7-19 are disconnected, and the moving breaking contacts 3-17 and 5-7 are closed; In the case of a fault, UZ≥UB, relay J will act, the moving contacts 1-3, 7-19 will be closed, and the moving break contacts 3-17, 5-7 will be disconnected.

3.2.2 For the zero-sequence overvoltage relay in normal operation, UZ<UB, relay J will not operate, the moving contacts 1-3 and 7-19 are disconnected, and the moving disconnection contacts 3-17 and 5-7 are closed; In the case of a fault, UZ≥UB, relay J will act, the moving contacts 1-3, 7-19 will be closed, and the moving break contacts 3-17, 5-7 will be disconnected.

3.3 The use of high-efficiency integrated circuits and components, with stable performance, high reliability, high accuracy of the action value, small discrete value, wide setting range, fast action and return speed, good return coefficient, small load on the transformer, and vibration resistance , Anti-interference and high insulation level.

3.4 The protection setting value is set by the dial switch on the relay panel, and the setting calculation formula is indicated. The setting is intuitive and convenient, and the debugging is simple and convenient. No adjustment is required on site.

3.5 The product installation structure includes embedded board rear wiring and protruding board front wiring as well as standard 35mm rail type terminal block wiring, which is convenient for on-site installation and has strong versatility.

Contact Us
Shenzhen Renergy Electric Equipment Co., Ltd.
Address: 102 on the fourth and first floors of Building A, Building C, Shangxue Technology Industrial City, Xinxue Community, Bantian Street, Longgang District, Shenzhen
Tel:0755-89325335    84505292
Fax:0755-89325332
E-mail:sz_ruineng@vip.163.com
Url:www.bddsjc.com


Scan for more
? 2020 深圳瑞能電氣設(shè)備有限公司 All Rights Reserved 粵ICP備13081107號(hào)