1. Application range

Overcurrent relays are used to distinguish the overload and short-circuit protection of power equipment such as generators, transformers, and transmission lines.

The low current relay is used as a blocking element for PT disconnection.

It can completely solve the defects of contact jitter, refusal to move when electromagnetic relays are operating, low setting accuracy, and return coefficients affected by residual magnetism. It can replace DL-31, DL-32 and DL-7 electromagnetic relays.


2. Model definition

20140429140160386038.jpg



3. Working principle and main performance

3.1 Working principle:

The AC current is converted by the converter to the AC voltage required by the series of relays; then the harmonics other than 50HZ are filtered through the 50HZ bandpass; then the DC voltage is sent to the tuning loop through rectification and filtering; the tuning loop depends on changing the amplifier's amplification Multiplier to change the setting value; the output voltage UZ of the setting loop is compared with the threshold voltage UB through the level detector; then the output of the relay J is driven to act.

3.2 Action process of low current and over current relay (take AK11 structure relay as an example):

3.2.1 For the over-current relay in normal operation, UZ<UB, relay J does not act, the moving contacts 1-3 and 7-19 are disconnected, and the moving breaking contacts 3-17 and 5-7 are closed; In the case of UZ≥UB, the relay J will act, the moving contacts 1-3 and 7-19 are closed, and the moving breaking contacts 3-17 and 5-7 are disconnected.

3.2.2 For low-current relays, under normal operation conditions UZ>UB, relay J does not operate, the moving contacts 1-3 and 7-19 are disconnected, and the moving breaking contacts 3-17 and 5-7 are closed; In the case of failure, UZ≤UB, relay J will act, moving-on contacts 1-3, 7-19 are closed, and moving-break contacts 3-17, 5-7 are open.

3.3 The use of high-efficiency integrated circuits and components, with stable performance, high reliability, high accuracy of the action value, small discrete value, wide setting range, fast action and return speed, good return coefficient, small load on the transformer, and vibration resistance , Anti-interference and high insulation level.

3.4 The protection setting value is set by the dial switch on the relay panel, and the setting calculation formula is indicated. The setting is intuitive and convenient, and the debugging is simple and convenient. No adjustment is required on site.

3.5 The product installation structure includes embedded board rear wiring and protruding board front wiring as well as standard 35mm rail type terminal block wiring, which is convenient for on-site installation and has strong versatility.